Rigid conduit bodies are regulated by the National Electrical Code (NEC) under Article 314, which governs outlet, device, pull, and junction boxes. Conduit bodies fall under this category because they provide access for conductor pulling, splicing, and maintenance. To ensure installations remain safe and code-compliant, the following NEC requirements must be observed:

1. Marking & Volume Capacity (NEC 314.16)

  • All conduit bodies must be permanently marked with their internal volume capacity in cubic inches (cu in).
  • The maximum number and size of conductors permitted is determined by this volume marking.
  • Example: An LB conduit body marked “12 cu in” can only accommodate a set number of 12 AWG conductors, based on NEC Table 314.16(B).

2. Conductor Fill Calculations

  • Each insulated conductor is assigned a volume allowance depending on wire gauge (e.g., 12 AWG = 2.25 cu in).
  • Equipment grounding conductors are counted once for the largest size present.
  • Devices (switches, receptacles) count as two conductors of the largest size connected.
  • Technical Note: Overfilling beyond the listed volume capacity is a violation of NEC 314.16 and can result in overheating and insulation damage.

3. Accessibility Requirements (NEC 314.29)

  • All conduit bodies must remain accessible after installation.
  • They cannot be concealed behind drywall, plaster, or permanently installed building materials.
  • Covers must be removable for maintenance, splicing, and inspection.

4. Bending Radius & Wire Pulling (NEC 300.34)

  • Conduit bodies are often installed at 90° changes in direction. NEC requires minimum bending radius for conductors to prevent insulation stress.
  • Improperly sized or selected conduit bodies can lead to failed inspections if the internal volume or radius is insufficient for the conductor size.

5. UL Listing & Product Standards

  • Rigid conduit bodies must comply with UL 514A (Metallic Conduit Bodies) or UL 514B (Nonmetallic Conduit Bodies).
  • UL testing ensures mechanical strength, corrosion resistance, and dimensional conformity for threaded hubs.
  • UL certification marks should be visible on every body and cover.

Technical Application Examples by Conduit Body Type

LB Conduit Body

  • Configuration: Straight-through conduit entry with a 90° change and rear cover access.
  • Applications: Service entrance conduits, outdoor meter bases, vertical-to-horizontal transitions.
  • Compliance Tip: Ensure conductor fill is calculated based on cubic inch marking; often used where NEC requires an accessible pull point at long conduit runs.

LL Conduit Body

  • Configuration: 90° left-hand turn with cover on the left side.
  • Applications: Tight wall spaces where conduit must bend left toward electrical panels or equipment.
  • Compliance Tip: NEC requires that the cover remain accessible; do not conceal in finished walls.

LR Conduit Body

  • Configuration: 90° right-hand turn with cover on the right side.
  • Applications: Utility rooms, stairwells, or corridors where conduit exits to the right.
  • Compliance Tip: Always check minimum bending radius if pulling larger conductors (e.g., 1/0 AWG feeders).

T Conduit Body

  • Configuration: Three conduit openings in a “T” shape for branching circuits.
  • Applications: Industrial plants, commercial lighting systems, branch circuits for receptacles or HVAC equipment.
  • Compliance Tip: NEC requires that branch splices within T bodies respect conductor fill limits; ensure cubic inch volume is adequate for conductor count.

C Conduit Body

  • Configuration: Two straight-through entries opposite each other, cover on the side.
  • Applications: Long conduit runs (e.g., parking garages, warehouses, underground raceways) to allow intermediate pulling points.
  • Compliance Tip: NEC 300.34 requires that long conductor pulls incorporate accessible pull points at required intervals—C bodies fulfill this requirement.

Field Example: NEC Code-Compliant Installation

Consider a commercial warehouse where a 150-foot run of 1-inch rigid conduit carries 12 AWG THHN conductors. NEC 300.34 requires pull points at intervals to prevent conductor damage. Installing C conduit bodies every 100 feet provides code compliance, while an LB body at the wall penetration ensures both accessibility and safe wire pulling radius.