Figure 6 Irreversible Compression Connector 250-500 MCM | Dual
Shipping calculated at checkout
SKU: 610-23158
In stock
Made to order. Utility-spec irreversible grounding connectors ship from our production line, typically 6-8 weeks. Volume pricing: trade desk.
Figure 6 irreversible compression connectors join two continuous parallel conductors in power distribution and grounding applications. The compact profile simplifies taping in tight enclosures. Pre-filled anti-oxidant compound inhibits corrosion at the interface. Rated for direct burial installations and lightning protection systems.
Specifications
- Conductor range: 250-500 MCM to #4 SOL / #2 STR
- Configuration: Two continuous parallel conductors
- Voltage rating: 600V
- Temperature rating: 90°C
- Material: Copper alloy
- Pre-filled with anti-oxidant compound
- UL 467 listed
- UL96 listed for lightning protection
- Suitable for direct burial
Cross-Reference
Equivalent to Burndy and Blackburn Figure 6 type irreversible compression connectors. Conversions Tech specifications match industry-standard dimensions and die index numbers for common compression tools.
FAQ
What conductor combinations does this connector accept?
The Figure 6 connector accommodates 250-500 MCM on one side and #4 SOL or #2 STR on the opposite side, configured for two continuous parallel conductors.
Is this connector rated for direct burial?
Yes. The connector carries UL 467 listing and is specified for direct burial applications.
What compression tool die is required?
Use the die index specified for Figure 6 connectors matching 250-500 MCM conductor range. Verify die compatibility with your tool manufacturer's chart before installation.
Cross-Reference & Application: 610-23158
| Brand | Series / Part | Notes |
|---|---|---|
| Burndy HYGROUND / HYTAP | YG6C-class* | irreversible compression grounding, UL 467, direct burial - supply-house pricing typically 2-3x CT $40.15 |
| Panduit StructuredGround | compression grounding series* | match by conductor range |
| nVent ERICO | Cadweld (exothermic alt.) | weld-based alternative - compression installs faster, no powder/mold |
Where & why irreversible compression
NEC 250.64(C) requires grounding electrode conductors to be continuous or joined with irreversible compression connectors or exothermic welding - standard mechanical clamps are not permitted for buried or concealed GEC splices. These UL 467 listed connectors are rated for direct burial in earth or concrete. Range: fig-6 250-500.
How to crimp
Single crimp with a 12-ton class dieless or U-die hydraulic tool (Burndy Y35/Y750 class, index per size). CT stocks compatible crimp tools and dies at distributor pricing - the same tool runs our full lug and grounding line.
*Cross by published conductor/rod range - verify for your application. Trademarks belong to their owners.
Why Pros Buy Direct from Conversions Tech
Engineered in the USA. Our U.S.-based engineering team designs and specifies our core product lines, and every product we carry — designed in-house or built to our exact specifications by certified partner factories — is quality-verified before it ships. UL/CSA listed where required, NEC compliant.
Cross-reference savings. Direct equivalents to Burndy, Hubbell, and other OEM part numbers at up to 30% less — same specs, same certifications, without the big-brand markup.
Real technical support. Need a torque spec, die reference, or an OEM quote? You’ll speak directly with the Conversions Tech engineering desk — not a script reader — for instant answers, custom kitting, and private-label options.
Fast US fulfillment. Orders in by 2PM ET ship same day from our US warehouse, nationwide ground and expedited.