Copper split bolt connectors, 8 AWG through 500 kcmil — high-strength copper-alloy bodies, 600 V / 90°C, UL 486A/B and UL 467 class, suitable for direct burial in earth or concrete. Ten sizes cover the same breaks as ILSCO Type IK and cross directly to Burndy SERVIT® KS, Blackburn Type H, and NSI N-series. Stocked; same-day shipping by 2PM ET; trade accounts on Net-30.

Sizing: pick by the larger conductor first — the run must sit inside the connector's equal main and tap range — then confirm the tap is at or above the minimum tap figure. Copper-alloy split bolts are for copper and copperweld only; aluminum or Cu/Al work needs a dual-rated body with a spacer. Torque to the marked value and insulate to the conductor rating per NEC 110.14(B).

Where they belong: service and feeder taps in troughs and wireways, bonding jumpers, accessible grounding electrode conductor taps, ground bars, temporary power, and repair splices. Where they don't: buried or encased GEC splices — NEC 250.64(C)(1) requires irreversible compression or exothermic weld there.

Cross-reference — copper split bolts

CT Part Equal main & tap Min tap Burndy KS ILSCO IK Blackburn H NSI Torque
610-00812 8 STR–12 SOL 16 KS15 IK-8N / IK-8 8H, 8H3 N-8* 80 in-lb
610-00610 6–10 SOL 16 KS17 IK-6N / IK-6 6H3, 6H N-6 165
610-0048 4–8 SOL 16 KS20 IK-4N / IK-4 4H N-4* 165
610-00261 2 STR–6 SOL 14 KS22, KS23 IK-2N / IK-2 1H N-2* 275
610-00104 1/0 STR–4 SOL 14 KS25 IK-1/0N / IK-1/0 10H N-1/0* 385
610-00204 2/0 STR–2 SOL 14 KS26 IK-2/0 20H N-2/0* 385
610-00302 3/0 STR–2 SOL 12 KS27 IK-3/0 30H N-3/0* 500
610-25001 250 kcmil–1/0 10 KS29 IK-250 40H N-250 650
610-35040 350 kcmil–4/0 8 KS31 IK-350 350M N-350* 650
610-00500 500–250 kcmil 8 KS34 IK-500 500M N-500* 825

Crosses identify copper-alloy split bolts of equivalent published range on the same UL 486A basis; dual-rated Cu/Al bodies (Burndy KSU, ILSCO SK, Blackburn HPS/HPW) are a separate class. *NSI numbers follow the family's max-size naming; verify on datasheet. Torque values are for maximum conductors — follow the marking on the connector.

Guides: Split Bolt Connectors: Sizing, Torque, Taping, and Where the NEC Won’t Let You Use One · Split Bolt Cross-Reference Chart · Contractor & distributor pricing →