CT 610-24107 — UL 467 irreversible compression C-tap grounding connector for a 3/0 AWG–250 MCM run with a 3/0 AWG–250 MCM tap — equal-size run and tap for grid-to-grid tees. The open C-body hooks over an uncut run conductor. Listed for direct burial and concrete encasement. Direct cross for Burndy HYGROUND HYTAP™ YGHC29C29 — same 12-ton tool platform, same die.
| Part No. | 610-24107 |
|---|---|
| Type | C-tap, run + tap |
| Run range | 3/0 AWG–250 MCM Cu |
| Tap range | 3/0 AWG–250 MCM Cu |
| Material | High-conductivity wrought copper |
| Listings | UL 467 grounding & bonding; direct burial / concrete encasement |
| Tooling | 12-ton U-die hydraulic (Y750/PAT750/Y46 class); die index stamped on body |
Cross-reference
| Manufacturer | Part No. | Covers | Die index |
|---|---|---|---|
| Burndy HYGROUND | YGHC29C29 | 3/0 str–250 kcmil run or 1/2"–5/8" rod; 3/0 str–250 kcmil tap | 997 (U997), 1 crimp |
Cross-references identify equivalent function and conductor/rod range; verify die selection against the index stamped on the connector.
Where it's used
- Full-size grid tees — 3/0–250 MCM branch runs off 3/0–250 MCM mains on substation and industrial mats
- Buried grid junctions with no access box (NEC 250.68(A) Exception)
- Ground ring extensions and loop closures on existing systems without cutting the run
How to install
Wire-brush both conductors to bright metal, hook the C over the uncut run, lay the tap in the saddle with tail past the connector ends, and crimp with the stamped die index until the dies fully bottom — center first, working outward. Full field procedure: How to Crimp Irreversible Compression Grounding Connectors.
Why irreversible compression
NEC 250.64(C)(1) permits grounding electrode conductor splices only by irreversible compression or exothermic welding. Compression installs in wet trenches with no hot-work permit, and every crimp embosses its die index for inspection. More: Where, How, and Why to Use Irreversible Compression Grounding.
Made to order — ships from our production line, typically 6–8 weeks. Volume and project pricing through the trade desk.
Why Pros Buy Direct from Conversions Tech
Engineered in the USA. Our U.S.-based engineering team designs and specifies our core product lines, and every product we carry — designed in-house or built to our exact specifications by certified partner factories — is quality-verified before it ships. UL/CSA listed where required, NEC compliant.
Cross-reference savings. Direct equivalents to Burndy, Hubbell, and other OEM part numbers at up to 30% less — same specs, same certifications, without the big-brand markup.
Real technical support. Need a torque spec, die reference, or an OEM quote? You’ll speak directly with the Conversions Tech engineering desk — not a script reader — for instant answers, custom kitting, and private-label options.
Fast US fulfillment. Orders in by 2PM ET ship same day from our US warehouse, nationwide ground and expedited.