Two-Hole Copper Compression Lug 3/0 AWG 3/8" Stud | 35kV 90°C
Shipping calculated at checkout
SKU: 210-98053B
1000 in stock
The Conversions Tech two-hole copper compression lug is engineered for secure termination of 3/0 AWG copper conductors in medium-voltage power distribution, industrial control panels, and utility infrastructure. The short barrel design with chamfered entry facilitates wire insertion, while the integrated sight window enables visual verification of proper conductor seating prior to compression. Two-hole pad configuration provides mechanical stability and load distribution on bus bars and equipment terminals.
Specifications
- Material: Seamless Electro-Tin Plated Copper
- Conductor Size: 3/0 AWG
- Stud Size: 3/8 Inch
- Pad Holes: 2
- Pad Hole Spacing: 1 Inch
- Pad Dimensions: 1.937" Length x 0.885" Width x 0.125" Thickness
- Overall Length: 3.126 Inches
- Barrel Type: Standard
- Barrel Length: 0.75 Inch
- ID x OD: 0.484" Inner Diameter x 0.609" Outer Diameter
- Barrel Entry: Chamfered
- Die Index: I-50
- Voltage Rating: 35 kV
- Temperature Rating: 90°C
- Color Code: Orange
Cross-Reference
Equivalent to Burndy YAV, Ilsco IAV, and Panduit LCC two-hole compression lug form factors for 3/0 AWG applications. Conversions Tech lugs are built to equivalent dimensional and electrical specifications at reduced lead times and competitive pricing.
FAQ
What crimping tool and die set is required for this lug?
Use a compression tool with die index I-50. The die index is stamped on the lug barrel and must match the tool die specification for proper compression geometry.
Is this lug rated for 35kV shielded cable applications?
The 35kV voltage rating applies to the lug insulation level when properly installed with compatible stress control and insulation systems. Verify system compatibility with your cable manufacturer specifications.
Why does this lug have two mounting holes?
The 1-inch spaced two-hole pad prevents lug rotation under fault conditions or vibration, distributing mechanical stress across both fasteners. Required by NEC 250.70 for grounding electrode conductor connections and recommended for heavy-current bus applications.
Why Pros Buy Direct from Conversions Tech
Engineered in the USA. Our U.S.-based engineering team designs and specifies our core product lines, and every product we carry — designed in-house or built to our exact specifications by certified partner factories — is quality-verified before it ships. UL/CSA listed where required, NEC compliant.
Cross-reference savings. Direct equivalents to Burndy, Hubbell, and other OEM part numbers at up to 30% less — same specs, same certifications, without the big-brand markup.
Real technical support. Need a torque spec, die reference, or an OEM quote? You’ll speak directly with the Conversions Tech engineering desk — not a script reader — for instant answers, custom kitting, and private-label options.