Which Compression Lug for Which Wire Gauge: 10 AWG to 1000 kcmil Buying Table

Purchasing calls with the conductor size. The estimator needs the lug part number. This is the working table between the two: for each common gauge, the lug family, barrel and stud choices, the die index and color, and where that size usually shows up. Copper Class B building wire (THHN, XHHW-2, USE-2) unless noted. For DLO, welding and battery cable, see the flex lug guide.

Gauge by gauge

Conductor Typical circuit Lug to order Studs stocked Die index / color Notes
10 AWG Branch, equipment grounds, control power 1-hole standard barrel #10, 1/4" I-21 red (shared with 8) 25-packs. Long barrel where the panel builder specs it.
8 AWG Branch, EGC, PV homeruns 1-hole standard or long barrel; 2-hole for ground bars #10, 1/4", 5/16", 3/8" I-21 red Highest volume small lug. Tin plated for PV wire.
6 AWG Feeders to 65 A, grounding electrode conductor, solar 1-hole and 2-hole, standard or long #10, 1/4", 5/16", 3/8", 1/2" I-24 blue 2-hole on 3/4" spacing for ground bars.
4 AWG Feeders to 85 A, EGC for 200 A services 1-hole and 2-hole, standard or long #10, 1/4", 5/16", 3/8", 1/2" I-29 gray Long barrel on vibration and generator work.
3 AWG 100 A feeders 1-hole standard or long 1/4", 5/16", 3/8", 1/2" I-33 brown Less common; keep in the kit for service upgrades.
2 AWG 115 to 130 A feeders, 200 A service grounds 1-hole and 2-hole, standard or long #10, 1/4", 5/16", 3/8", 1/2" I-33 brown Long barrel two-hole on switchgear.
1 AWG 130 A feeders 1-hole and 2-hole, standard or long 1/4", 5/16", 3/8", 1/2" I-37 green Two-hole on 7/8" or 1" spacing; check the pad.
1/0 AWG 150 A feeders, 200 A residential service 1-hole and 2-hole, standard or long 1/4", 5/16", 3/8", 1/2" I-42 pink Most common feeder size on small commercial.
2/0 AWG 175 A feeders, generator leads 1-hole and 2-hole, long barrel preferred 1/4", 5/16", 3/8", 1/2", 5/8" I-45 black DLO 2/0 needs a flex lug, not this.
3/0 AWG 200 A feeders and services 1-hole and 2-hole, long barrel preferred 1/4", 5/16", 3/8", 1/2" I-50 orange Two-hole NEMA spacing on switchgear.
4/0 AWG 230 A feeders, 200 A aluminum service equivalents in copper 1-hole and 2-hole, long barrel 1/4", 3/8", 1/2" I-54 purple Long barrel from here up: two crimps, QA pull tests.
250 kcmil 255 A feeders, parallel runs 1-hole and 2-hole, long barrel 1/4", 3/8", 1/2", 5/8" I-62 yellow First size with 5/8" studs on gear pads.
300 kcmil 285 A feeders 1-hole and 2-hole, long barrel 3/8", 1/2", 5/8" I-66 white Common on 400 A services.
350 kcmil 310 A feeders, 400 A service parallels 1-hole and 2-hole, long barrel 3/8", 1/2", 5/8" I-71 red Stock two-hole 1/2" for switchgear.
400 kcmil 335 A feeders 1-hole and 2-hole, long barrel 1/2", 5/8" I-76 blue Less common; confirm before stocking deep.
500 kcmil 380 A, the standard parallel feeder conductor 2-hole long barrel first, 1-hole second 3/8", 1/2", 5/8" I-87 brown Data centers and switchgear pull this by the thousand.
600 kcmil 420 A 2-hole long barrel 3/8", 1/2", 5/8" I-94 green Confirm lug pad clearance in gear.
750 kcmil 475 A, utility and data center feeders 2-hole long barrel 1/2", 5/8" I-99 black Largest common size; 12 ton tool required.
1000 kcmil 545 A, generation and utility 1-hole and 2-hole long barrel 1/2", 5/8" I-115 Special order pads; check dimensions.

Ampacities are 75°C column NEC 310.16 copper for orientation only; the engineer's schedule governs. Die indexes follow the industry color code used by Burndy, Greenlee, T&B and the Conversions Tech CTTY series; confirm the index printed on the lug.

How to pick within a size

  1. Holes. One hole for equipment terminals and most panels. Two hole for bus bars, switchgear pads, ground bars and anywhere the spec says NEMA drilling.
  2. Stud. Read the terminal or pad. Do not oversize the hole; a 1/2" hole on a 3/8" bolt loses contact area.
  3. Barrel. Standard barrel where space is tight and the conductor is 2/0 or smaller. Long barrel on 4/0 and up, on generators and rotating equipment, and on any job with pull testing. See long barrel vs standard barrel.
  4. Plating. Tin plated for everything outdoors, on tinned conductor, in damp rooms and in battery or DC work. All Conversions Tech copper lugs are tin plated.
  5. Die. One die per size, matched to the lug index. Buy the die with the first box of a new size.

Stocking list for a service truck or panel shop

Standard barrel 1-hole in 8, 6, 4, 2, 1/0, 2/0, 3/0 and 4/0 with 1/4", 5/16" and 3/8" studs; long barrel 2-hole in 1/0, 2/0, 4/0, 250, 350 and 500 with 3/8" and 1/2"; the die set from I-21 through I-87. That covers most service, feeder and switchgear work without a second trip.

Every lug page shows the conductor range, die index, dimensions and the Burndy, ILSCO and Panduit cross. Send a conductor schedule to CS@ConversionsTech.com for a takeoff; same-day shipping on in-stock items and case pricing for trade accounts.