Skip to content

90° Flag Compression Lug 10 AWG, 1/4" Stud, 25-Pack | Short Barrel, Tin-Plated Copper, UL 486A/B | CT-SB10-14-90

Sale price $24.50

Shipping calculated at checkout

🛡 Trade Pricing Program Contractors, wholesalers & distributors save 15–30% Apply — 60 seconds Sign In

SKU: CT-SB10-14-90-25

In stock

Shop with confidence

  • Same-day shipping by 2PM ET
  • UL / CSA listed products
  • Net 30-60 terms available
  • Engineering desk support
  • Competitive cross-reference pricing
  • Ach Direct Debit
  • American Express
  • Diners Club
  • Discover
  • Mastercard
  • PayPal
  • USDC
  • Visa

CT CT-SB10-14-90 — 90° flag compression lug, 10 AWG, 1/4" stud, short barrel. The barrel is bent 90° to the tongue so the conductor runs parallel to the mounting surface — the fix for gutters, panelboards, switchgear, transformer cabinets, and battery enclosures where a straight lug will not clear the cover or bend radius. Seamless electro-tin-plated copper with yellow color-code band and inspection window. Crosses to the Burndy HYLUG™ YA-L-90 family.

Part No. CT-SB10-14-90
Conductor 10 AWG Cu stranded (code / Class B); color code yellow
Stud hole 1/4", one hole
Barrel Short Barrel, 90° to tongue, internally chamfered, inspection window
Material / finish Seamless high-conductivity copper, electro-tin plated
Ratings 600 V and up to 35 kV, 90°C; UL 486A/B, CSA class; RoHS
Tooling Standard hex/U-die hydraulic crimpers; Burndy-index die number stamped on barrel; crimp count marked

Cross-reference

Manufacturer Part No. Notes
Burndy HYLUG™ YA10CL290* YA-L-90 one-hole 90° copper lug, 10 AWG, 1/4" stud — *pattern-derived, verify against Burndy catalog
Panduit LCA / LCAS flag class Pan-Lug™ 90° flag lugs by size and stud

Where it's used

  • Panelboard and switchgear terminations where conductor entry is perpendicular to the lug pad
  • Transformer cabinets, gutters, and wireways with tight bend clearance
  • Battery banks, UPS, and inverter DC feeds; bus-bar and ground-bar landings in telecom and data rooms
  • Motor terminal boxes and generator connections

How to install

Strip to the barrel depth plus 1/16", insert until the conductor shows in the inspection window, crimp with the die index stamped on the barrel (number of crimps as marked, starting nearest the tongue), and land on the stud with a flat washer, lock washer, and the torque specified for the stud size (typical: #10 20 in-lb, 1/4" 60 in-lb, 5/16" 120 in-lb, 3/8" 240 in-lb, 1/2" 500 in-lb). Selection guide: 90°, 45°, and Straight Compression Lugs — When to Bend the Barrel.

Stocked — same-day shipping on orders by 2PM ET. Volume and trade pricing through the trade desk.

Why Pros Buy Direct from Conversions Tech

Engineered in the USA. Our U.S.-based engineering team designs and specifies our core product lines, and every product we carry — designed in-house or built to our exact specifications by certified partner factories — is quality-verified before it ships. UL/CSA listed where required, NEC compliant.

Cross-reference savings. Direct equivalents to Burndy, Hubbell, and other OEM part numbers at up to 30% less — same specs, same certifications, without the big-brand markup.

Real technical support. Need a torque spec, die reference, or an OEM quote? You’ll speak directly with the Conversions Tech engineering desk — not a script reader — for instant answers, custom kitting, and private-label options.

Fast US fulfillment. Orders in by 2PM ET ship same day from our US warehouse, nationwide ground and expedited.