Long Barrel Two-Hole Compression Lug 3/0 AWG 1/2" Stud | 310A 90°C
Shipping calculated at checkout
SKU: 210-09967
123 in stock
The Conversions Tech long barrel two-hole compression lug terminates 3/0 AWG copper conductors in medium-voltage distribution, switchgear, and transformer applications. The extended barrel design maximizes contact surface area for high-current reliability, while the dual-hole pad configuration distributes mechanical load across two 1/2-inch studs. Orange color coding provides immediate wire size identification in crowded termination boxes. The chamfered cable entry and seamless electro-tin-plated copper construction resist corrosion and accommodate heavy-wall insulation without nicking.
Specifications
- Conductor Size: 3/0 AWG
- Stud/Bolt Size: 1/2"
- Pad Configuration: 2 holes
- Pad Hole Spacing: 1 3/4" (44.5 mm)
- Pad Dimensions: 1.437" L x 0.885" W x 0.125" thick
- Barrel Length: 1.5"
- Overall Length: 3.376" (93.5 mm / 3.68")
- Neck Length: 2.13" (54.1 mm)
- Inner Diameter: 0.484" (15.7 mm / 0.62")
- Outer Diameter: 0.609" (23.0 mm / 0.91")
- Width: 1.20" (30.5 mm)
- Thickness: 0.11" (2.7 mm)
- Hole Diameter: 0.51" (13.0 mm)
- Hole Spacing (alternate): 0.51" (13.0 mm)
- Material: Seamless electro-tin-plated copper
- Color Code: Orange
- Voltage Rating: 35 kV
- Maximum Ampacity: 310A
- Temperature Rating: 90°C
- Die Index: I-50
- Cable Entry: Chamfered
- Design: No sight window
- Certifications: UL Recognized, CE Certified, RoHS Compliant
Cross-Reference
Equivalent to long-barrel two-hole compression lugs from major manufacturers. Form factor matches industry-standard 3/0 AWG two-hole terminals for use in substations, industrial motor controls, and power distribution equipment.
FAQ
What crimping tool is required for this lug?
Use a compression tool with I-50 die index. Verify die compatibility with your tool manufacturer; the long barrel requires full-length crimping to achieve rated ampacity.
Is this lug rated for outdoor or wet location use?
The tin-plated copper construction and 90°C temperature rating suit standard industrial environments. For specific environmental ratings, consult your local electrical code and application requirements.
Can I use this with fine-stranded flexible conductor?
This lug is specified for 3/0 AWG conductors. For fine-stranded or flexible cables, verify conductor diameter against the 0.484" inner barrel diameter and chamfered entry dimensions.
Direct Cross-Reference — Two-Hole NEMA (1.75″ centers), 3/0 AWG, 1/2 Inch stud
CT P/N 210-09967 is a dimensional and electrical equivalent replacement for:
| Manufacturer | Part Number |
|---|---|
| Panduit | LCC3/0-12 * |
| NSI Industries | L30N * |
* Cross derived from manufacturer part-numbering pattern; verify against datasheet for critical applications. All trademarks are property of their respective owners and are used for compatibility identification only. Conversions Tech products meet the same UL 486A dimensional and electrical standards at distributor-direct pricing.
Why Pros Buy Direct from Conversions Tech
Engineered in the USA. Our U.S.-based engineering team designs and specifies our core product lines, and every product we carry — designed in-house or built to our exact specifications by certified partner factories — is quality-verified before it ships. UL/CSA listed where required, NEC compliant.
Cross-reference savings. Direct equivalents to Burndy, Hubbell, and other OEM part numbers at up to 30% less — same specs, same certifications, without the big-brand markup.
Real technical support. Need a torque spec, die reference, or an OEM quote? You’ll speak directly with the Conversions Tech engineering desk — not a script reader — for instant answers, custom kitting, and private-label options.
Fast US fulfillment. Orders in by 2PM ET ship same day from our US warehouse, nationwide ground and expedited.