Long Barrel Compression Lug 2 AWG 1/2" Bolt | 170A 35kV 90°C Tin-Plated
Shipping calculated at checkout
SKU: 210-09856
980 in stock
This long barrel one-hole compression lug terminates 2 AWG copper conductors to 1/2-inch studs in industrial and commercial power distribution systems. The extended barrel length increases contact surface area and mechanical grip compared to standard barrel designs, reducing loosening from thermal cycling and vibration in switchgear, transformers, panelboards, and motor control centers. The electro-tin plated copper construction resists oxidation and maintains conductivity over long service life. Brown color coding provides quick wire size identification during installation and maintenance.
Specifications
- Conductor Size: 2 AWG
- Stud/Bolt Size: 1/2"
- Terminal Material: Tin-plated copper
- Color Code: Brown
- Overall Length (L): 57.5 mm (2.27")
- Barrel Length (L1): 28.7 mm (1.13")
- Barrel Outer Diameter (D): 17.7 mm (0.70")
- Barrel Inner Diameter (D1): 10.7 mm (0.42")
- Conductor Entry Diameter (D2): 8.5 mm (0.33")
- Palm Width (B): 24.5 mm (0.96")
- Center Height (E): 13.1 mm (0.51")
- Palm Thickness (F): 1.9 mm (0.07")
- Current Rating: 170A
- Voltage Rating: 35 kV
- Temperature Rating: 90°C
- UL Recognized: Yes
- CE Certified: Yes
- RoHS Compliant: Yes
Cross-Reference
Equivalent form factor to long barrel compression lugs from major electrical manufacturers. Specified by Conversions Tech engineering and manufactured to these dimensions and ratings by certified partner factories.
FAQ
What crimping tool and die are required for this lug?
Use a compression tool with hex or indent dies sized for 2 AWG long barrel lugs. The 28.7 mm barrel length requires a die set compatible with extended barrel terminals. Verify die index marks align with barrel length for full compression.
Is this lug rated for medium voltage applications?
Yes, the 35 kV voltage rating suits medium voltage terminations up to that level when used with appropriate insulation and clearances per NEC and NEMA standards. Confirm system voltage and insulation requirements with your application engineer.
Can this lug be used for both copper and aluminum conductors?
No, this lug is designed for copper conductors only. The dimensions, plating, and ampacity ratings are specified for copper cable. For aluminum conductors, specify a lug rated for aluminum or dual-rated copper/aluminum with appropriate oxide-inhibiting compound.
Why Pros Buy Direct from Conversions Tech
Engineered in the USA. Our U.S.-based engineering team designs and specifies our core product lines, and every product we carry — designed in-house or built to our exact specifications by certified partner factories — is quality-verified before it ships. UL/CSA listed where required, NEC compliant.
Cross-reference savings. Direct equivalents to Burndy, Hubbell, and other OEM part numbers at up to 30% less — same specs, same certifications, without the big-brand markup.
Real technical support. Need a torque spec, die reference, or an OEM quote? You’ll speak directly with the Conversions Tech engineering desk — not a script reader — for instant answers, custom kitting, and private-label options.
Fast US fulfillment. Orders in by 2PM ET ship same day from our US warehouse, nationwide ground and expedited.